Cold start allows the UPS to start on battery power. In this way, the UPS can operate without being connected to the electrical system.

The 1300 M1 line features three and four battery compartments. In this sense, different power backup configurations can be realized.

They grant a high efficiency in the energy consumption of the 1300 M1 line, reaching a level of 94%.

The 1300 M1 line has two communication protocols: SNMP and Modbus. In this way, it is possible to carry out remote, safe and reliable monitoring of the UPS operation.

In a simple and effective way it is possible to parallel up to 4 UPS of the 1300 M1 line. This function allows the user to have a more secure backup chain and increase its protection capacity without losing the initial investment.

Unity power factor allows you to use the full capacity (kVA) of the UPS to support and protect your equipment. A highly efficient team is the best investment.
The high frequency UPS-IND HF 1300 M1 provides power backup solutions for critical loads, thanks to its three-level inverter with PWM type IGBT technology provides adaptive management to higher powers, operating at high speed and higher efficiency.
>
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Capacity (kW/ kVA) | 10/10 | 15/15 | 20/20 | 30/30 |
| Overload Protection | Thermal magnetic input circuit breaker and Thermal magnetic bypass circuit breaker | |||
| Voltage Range (Vac) | 156 a 260 (Line to Line): -29%, +18% (percentage of nominal voltage) | |||
| Phase | Three Phase Star, 3 Phases + Neutral + Ground, optional: Delta (3 Phases + Ground) | |||
| Frequency Range (Hz) | 40 ~ 70 | |||
| Input Power Factor | ≥ 0.99 at full load | |||
| THDi | ≤ 3% | |||
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| AC to AC Maximum Efficiency | 94 % | |||
| Overload Protection | Thermal magnetic output circuit breaker | |||
| Output Power Factor | 1.0 | |||
| Voltage (Vac) | 110/190, 115/200, 120/208 or 127/220 | |||
| Voltage Regulation Range (Vac) | ≤+/- 1 % | |||
| Frequency (Hz) | 60 +/- 0.1% (battery mode), optional: 50 Hz | |||
| Waveform | Pure sinosoidal wave | |||
| Harmonic Distortion THDv | ≤ 1% (Linear load), ≤ 4% (non linear load) | |||
| Transfer Time (ms) | 0.0 ms(True On Line) | |||
| Connection Type | Three phase star, 3 phases + neutral + ground, optional: delta (3 phases + ground) | |||
| Overload | << 105% continuous, 105% to 110% 60 min., 110% to 125% 10 min., 125% to 150% 60 s., > 150% immediate switch to bypass | |||
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Voltage (Vcd) | +/-96 ~ +/-120 (adjustable) | |||
| Battery Capacity | 20 x 9Ah 12 V | 32 x 9Ah 12 V | 40 x 9Ah 12 V | 64 x 9Ah 12 V |
| Battery Type | Lead Acid (Sealed & Maintenance Free) | |||
| Full load backup time (min) | 5 min standard (extended time available upon request) | |||
| Maximum Load Current (A) | Adjustable 1 a 10 | Adjustable 1 a 20 | ||
| Internal battery bank | Space for 60 Batteries (3 packs of 20) | Space for 80 Batteries (4 packs of 20) | ||
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Audible Noise (dB) | < 55, at 1 meter | |||
| Operating temperature (°C) | -5 ~ 40 | |||
| Relative humidity | 0 ~ 95% without Condensation | |||
| Maximum operating altitude (m.a.s.l.) | 2,000 at 100% | |||
| Cabinet | Baked electrostatic Epoxy coated Steel | |||
| Dimensions, height x width x depth (mm) | 1100 x 280 x 835 | 1250 x 320 x 880 | ||
| UPS net weight (kg) | 75 / 125*/ 150** | 93 / 173*/ 170 ** | 95 / 186*/ 172** | 112 / 269*/ 198** |
| UPS packaged weight (kg) | 95 / 145*/ 170** | 113 / 193*/ 190 ** | 115 / 206*/ 192** | 127 / 289*/ 218** |
*Weight with batteries included **Weight with transformer included
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Inverter | 3 level IGBT technology for higher efficiency and minimized interference to grid | |||
| Rectifier | High Efficiency PFC type with IGBT technology | |||
| Output Isolation Transformer | Optional | |||
| Battery Status | Real Time Online/Discharge Information | |||
| Thermal Dissipation (kBTU / h) | 2.05 | 3.07 | 4.10 | 6.15 |
| Internal Bypass | Two Bypass Modes: Automatic Static & Manual Bypass Switch for Maintenance | |||
| Paralleling | Parallelable by Capacity and/or Redundancy N + 1 (up to 4 units) | |||
| Certifications | UL-1778, CE-62040-1, CE 62040-2, ISO 9001:2015, NOM/td> | |||
| Communications Interface | RS485 + EPO, 5 dry contact output signals, 1 dry contact input, RS232, SNMP network card | |||
| Digital Touch Screen | Displays: Input and output voltage, Load capacity, Battery voltage, Operating Status Mimic and LEDs Indicators | |||
| Alarms | Low Battery, Abnormal Input, UPS Failure, etc. | |||
| Protection | Low Battery, Overload, Short Circuit, Over Temperature, etc. | |||
Instantly calculate equipment capacity by filling in the missing information: