BPA-IND 38

UPS Battery

BPA-IND 38

UPS Battery
12 V 38 Ah
Capacity
1 Year Warranty

UPS Batteries are ideal for high demand applications, provide extended life and prevent damage from micro short circuits.

  • Maintenance Free
  • Lead Calcium Grills
  • Augmented Resistance
  • AGM Separator
  • Gas Recombination
  • Superior Materials
Icono rayo
Maintenance Free
Sealed Lead Acid Batteries require zero maintenance.
Icono rayo
Lead Calcium Grills
Reduced gassing, self discharge and corrosion to provide long life expectancy and optimum operation.
Icono rayo
Augmented Resistance
Battery case with ABS materials for increased heat and impact resistance.
Icono rayo
AGM Separator
Withstands low temperatures, has low self discharge and significantly extends life expectancy-
Icono rayo
Gas Recombination
Gasses recombine to create humidity which reduces maintenance and lowers gassing.
Icono rayo
Superior Materials
High Purity Lead Acid Batteries ensure low self discharge.

Applications

Technical Specifications

Nominal Voltage 12 V
Nominal Capacity (20 hr) 38 Ah
Dimensions (mm)
(length x width x height)
197 (± 2) x 165 (± 2) x 170 (± 2)(170 ± 2 Total Height with Terminal)
Weight (kg) 12.2
Terminal T6
Container Material ABS
Rated Capacity 40.0 Ah / 2.0 A (20 hr, 1.80 V/cell, 25 ˚C)
38.0 Ah / 3.80 A (10 hr, 1.80 V/cell, 25 ˚C)
32.7 Ah / 6.55 A (5 hr,1.75 V/cell, 25 ˚C)
29.7 Ah / 9.89 A (3 hr,1.75 V/cell, 25 ˚C)
23.2 Ah / 23.2 A (1 hr,1.60 V/cell, 25 ˚C)
Max. Discharge Current 456 A (5s)
Internal Resistance 10 m Ω (aprox.)
Operating Temp.Range
Discharge -15 ~ 50 ˚C
 Charge 0 ~ 40 ˚C
Storage -15 ~ 40 ˚C
Nominal Operating Temp. Range 25 ± 3 ˚C
Cycle Use Initial Charging Current less than 11.4 A Voltage 14.4 ~ 15.0 V at 25 ˚C, Temp. Coefficient -30mV / ˚C
Uso en Standby No limit on Initial Charging Current Voltage
13.5 ~ 13.8 V a 25 ˚C, Temp. Coefficient -20mV / ˚C
Capacity affected by Temperature 103% = at 40 ˚C,
100% = at 25 ˚C,
86% = at 0 ˚C
Self Discharge INDUSCELL batteries may be stored for up to 6 months at 25 ˚C, and then a freshening charge is required. For higher temperatures the time interval will be shorter.