Uninterruptible Power Supply (UPS)

UPS IND HF 1300 M1

Uninterruptible Power Supply (UPS)

UPS IND HF 1300 M1

10 ~ 20 kVA
Capacity
+/- 1%
Voltage regulation
2 Year Warranty

The high frequency UPS-IND HF 1300 M1 provides power backup solutions for critical loads, thanks to its three-level inverter with PWM type IGBT technology provides adaptive management to higher powers, operating at high speed and higher efficiency.

  • On-line double conversion
  •  1.0 Power Factor
  • High Efficiency of 94%
  • Lower Footprint
  • Dual DSP for high reliability and performance
  • 2 Optional slot for SNMP and dry contact
  • 3 Level IGBT Technology Inverter
  • Dual input power supply: Mains and bypass
  • Anti-corrosion resistant coating for all PCB boards

UPS High Frequency

Icono rayo
On Line Double Conversion
Guarantees clean and stable voltage output despite irregularities on the input.
Icono rayo
1.0 Power Factor
The 1.0 power factor ensures efficiency and performance, optimizing the electrical system
Icono rayo
Dual DSP
Dual Digital Signal Processor (DSP) high precision and high speed control for maximum system performance.
Icono rayo
High Efficiency
AC/AC efficiency up to 94%
Icono rayo
Lower Footprint
The new generation provides a better user experience in a smaller footprint.
Icono rayo
2 Optional slot
2 Optional slot for SNMP and dry contact
Icono rayo
3 Level IGBT
3 Level IGBT Technology Inverter
Icono rayo
Dual input
Dual input power supply: Mains and bypass
Icono rayo
Anti-corrosion PCB boards
Anti-corrosion resistant coating for all PCB boards

Applications

Alarm and Security Systems
Alarm and Security Systems
Audiovisual Systems
Audiovisual Systems
Audiovisual Systems
Audiovisual Systems
Banks
Banks
Commercial buildings
Commercial buildings
Commercial Security Systems
Commercial Security Systems
Computer Rooms
Computer Rooms
Data Centers
Data Centers
Regional Office Building
Regional Office Building
Robotics
Robotics
Telecommunication
Telecommunication

Technical Specifications

Model UPS-IND HF
1310 M1
1315 M1
1320 M1
Capacity (W/ VA) 10000/10000 15000/15000 20000/20000
Overload Protection Thermal magnetic input circuit breaker and Thermal magnetic bypass circuit breaker
Voltage Range (Vac) 156 a 260 (Line to Line): -29%, +18%
Phase Three Phase Star, 3 Phases + Neutral + Ground, optional: Delta (3 Phases + Ground
Frequency Range (Hz) 40 ~ 70
Input Power Factor ≥ 0.99 at full load
THDi ≤ 3%
Model UPS-IND HF
1310 M1
1315 M1
1320 M1
AC to AC Maximum Efficiency 94 %
Overload Protection Thermal magnetic output circuit breaker
Output Power Factor 1.0
Voltage (Vac) 110/190, 115/200, 120/208 o 127/220
Voltage Regulation Range (Vac) ≤+/- 1 %
Frequency (Hz) 60 +/- 0.1% (Battery mode), Optional: 50 Hz
Waveform Pure Sinosoidal Wave
Harmonic Distortion THDv ≤ 1% (Linear load), ≤ 4% (Non linear load)
Transfer Time (ms) 0.0 ms(True On Line)
Connection Type Three Phase Star, 3 Phases + Neutral + Ground, optional: Delta (3 Phases + Ground)
Overload << 105% continuous, 105% to 110% 60 min., 110% to 125% 10 min., 125% to 150% 60 s., > 150% immediate switch to Bypass
Model UPS-IND HF
1310 M1
1315 M1
1320 M1
Voltage (Vcd) +/-96 ~ +/-120 (adjustable)
Battery Capacity 20 x 9Ah 12 V 32 x 9Ah 12 V 40 x 9Ah 12 V
Battery Type Lead Acid (Sealed & Maintenance Free)
Full load backup time (min) 5 min Standard (Extended Time available upon request)
Maximum Load Current (A) Adjustable 1 a 10 Adjustable 1 a 20
Battery Bank Internal: with space for 60 Batteries (3 packs of 20)
Model UPS-IND HF
1310 M1
1315 M1
1320 M1
Audible Noise (dB) < 55, at 1 meter
Operating Temperature (°C) -5 ~ 40
Relative Humidity 0 ~ 95% without Condensation
Maximum Operating Altitude (m.a.s.l.) 2,000 at 100%
Cabinet Baked electrostatic Epoxy coated Steel
Dimensions, height x width x depth (mm) 1100 x 300 x 800
UPS Weight (kg) 65 / 119 (with batteries) 65 / 152 (with batteries) 65 / 173 (with batteries)
Model UPS-IND HF
1310 M1
1315 M1
1320 M1
Inverter 3 level IGBT technology for higher efficiency and minimized interference to grid
Rectifier High Efficiency PFC type with IGBT technology
Output Isolation Transformer Optional
Battery Status Real Time Online/Discharge Information
Thermal Dissipation (kBTU / h) 2.05 3.07 4.10
Internal Bypass Two Bypass Modes: Automatic Static & Manual Bypass Switch for Maintenance
Paralleling Parallelable by Capacity and/or Redundancy N + 1 (up to 4 units)
Certifications CE-62040-1, CE 62040-2, ISO 9001:2015, NOM/td>
Communications Interface RS485 + EPO, 5 dry contact output signals, 1 dry contact input, RS232, SNMP network card
Digital Touch Screen Displays: Input and output voltage, Load capacity, Battery voltage, Operating Status Mimic and LEDs Indicators
Alarms Low Battery, Abnormal Input, UPS Failure, etc.
Protection Low Battery, Overload, Short Circuit, Over Temperature, etc.