UPS-IND HF 1300 (800-1200)

Uninterruptible Power Supply (UPS)

UPS-IND HF 1300 (800-1200)

Uninterruptible Power Supply (UPS)
800~1200 kVA
Capacity
+/-1%
Voltage regulation
2 Year Warranty

The high frequency UPS provides power backup solutions for critical loads such as telecommunications, laboratory equipment, intelligent buildings, glass and metal industries, PLC systems and power plants.

  • On Line Double Conversion
  • 1.0 Power Factor
  • Battery Backup
  • 97% High Efficiency
  • Parallelable Technology
  • DSP Control
  • IGBT Technology
  • SNMP Network Card
  • Electronic Bypass

Uninterrupted Power, True On Line

Icono rayo
On Line Double Conversion
Guarantees clean and stable voltage output despite irregularities on the input.
Icono rayo
1.0 Power Factor
1.0 Power factor ensures optimized efficiency and performance of complete electrical system.
Icono rayo
Power Factor Correction
Reduces gap between voltage and current for higher efficiency and functionality.
Icono rayo
Battery Backup
Ensures operational continuity with 5 minute standard battery backup time. Optional extended backup time may be added to adjust to specific needs.
Icono rayo
Parallelable Technology
Parallel by capacity or redundancy n + 1 (master-slave exempt); up to 8 units.
Icono rayo
DSP Control
Digital Signal Processor sustains high precision control and speed for optimal system performance.
Icono rayo
IGBT Technology
High efficiency and fast switching controller that adapts to high power applications.
Icono rayo
SNMP Network Card
Monitoring equipment alerts, controls and tracks current status of UPS from any off site location.
Icono rayo
Electronic Bypass
Automatic bypass ensures operational continuity in the event of a failure.

Video

Applications

Technical Specifications

UPS IND HF
13225
13800
131000
131200
13800
131000
131200
Capacity (kW / kVA) 800/800 1000/1000 1200/1200 800/800 1000/1000 1200/1200
Voltage (Vca) 120/208, 127/220 254/440, 266/460, 277/480
Overload Protection Thermal magnetic input circuit breaker and Thermal magnetic bypass circuit breaker
Online Voltage Range (Vca) +/- 20% at 100% Load, +/- 25% at 75% Load, +/- 30% at 50% Load
Phases Three Phase Star, 3 Phases + Neutral + Ground
Frequency(Hz) 50/60 ± 10 %
THDi ≤ 2 % (at 100% Load); ≤ 4 % (at 50% Load)
Input Power Factor ≥ 0.99
UPS IND HF
13225
13800
131000
131200
13800
131000
131200
Overload Protection Thermal magnetic output circuit breaker
Output Power Factor 1.0
Voltage (Vca) 120/208, 127/220 254/440, 266/460, 277/480
Voltage Regulation Range ± 1%
Frequency(Hz) 50/60 ± 0.1% (Battery Mode), 50/60 ± 1 ~5 (Online Mode)
Wave Form Pure Sinosoidal Wave, THD ≤ 1% (Linear Load); ‹ 3% (Nonlinear Load)
Transfer Time (ms) 0.0, True Online
Connection Type Star, 3 Phases + Neutral + Ground
Overload 110% 60 min; 125% 10 min; 150% 1 min
Efficency 97%
Load Imbalance Capacity 100%
UPS IND HF
13225
13800
131000
131200
13800
131000
131200
Voltage (Vcd) 384 – 528 Adjustable
Battery Type Lead Acid (Sealed & Maintenance Free) / (Optional Nickel Cadmium)
Full load backup time (min) 5 min Standard (Extended Time available upon request)
Maximum Load Current (A) 25 – 200
Battery Bank External Bank
UPS IND HF
13225
13800
131000
131200
13800
131000
131200
Audible Noise (dB) < 65, a 1 Meter
MTBF (hrs) 233,000
Operating Temperature Range (°C) -5 ~ 40
Relative Humidity 0 ~ 95% without Condensation
Maximum Operating Altitude (mamsl) 3,000
Finish IP 20, Baked Electrostatic Epoxy Coated Steel
Dimensions: height x width x depth (mm) 1950 x 2700 x 1000 1950 x 3800 x 1000 1950 x 3800 x 1200 1950 x 2700 x 1000 1950 x 3800 x 1000 1950 x 3800 x 1200
UPS Weight (kg)** 3400 4900 5300 2500 3800 3900
UPS IND HF
13225
13800
131000
131200
13800
131000
131200
Conversion Type Online Double Conversion (True Online)
Rectifier IGBT type with High Power Factor
Inverter Conmutation Elements GBT with PWM Pulse Width Management Technology
Filters PFC to Reduce Harmonic Distortion (2% RMS)
Battery Status Real Time Online/Discharge Information with 3% Precision
Thermal Dissipation (kBTU / h) 84.4 105.5 126.6 84.4 105.5 126.6
Internal Bypass Two Bypass Modes: Automatic Static & Manual Bypass Switch for Maintenance
Paralleling Parallelable by Capacity and/or Redundancy N + 1 (up to 8 units)
Certifications CE-IEC 62040 -1, ISO 9001:2015, NOM
Communication Interface RS485 / SNMP/ Dry Contacts / MODBUS
LCD Color Screen Backlight: Input/Output Voltage, Load Capacity, Battery Voltage, Operation Status
Alarm Overload, Abnormal Input, Low Battery, Failure
Protection Output Short Circuit, Overload, Overheating, Battery Low Voltage, High/Low Output Voltage

Request quote