The FAP-IND Harmonic Filter, designed to reduce harmonic current distortion, operates at frequencies of 50 Hz or 60 Hz, preventing malfunctioning of your equipment.
| FAP-IND Model | 5330 | 5350 | 53100 | 53150 | 53200 |
| Capacity (kVA) | 30 | 50 | 100 | 150 | 200 |
| Voltages (VAC) L-L | 208/220/240 | ||||
| Phases | 3 phases / 2 phases | ||||
| Frequency (Hz) | 50-60 Hz | ||||
| Consume (W) | 179 | 201 | 296 | 465 | 516 |
| Max. constant current Amp | 92 | 143 | 275 | 412 | 534 |
| Impedance characteristic | 5% | ||||
| Impedance characteristic | 95% @ 110% charge / 80% @ 150% charge | ||||
| Overload | 200% @ 3 minutes maximum | ||||
| Current harmonic distortion reduction | 40% to 50% reduction in distortion, for loads greater than 50% of capacity | ||||
| Recommended maximum voltage unbalance | +_1% | ||||
| Filter type | Reject Reactor | ||||
| FAP-IND Model | 5345 | 53100 | 53150 | 53200 | 53300 | 53500 |
| Capacity (kVA) | 45 | 100 | 150 | 200 | 300 | 500 |
| Voltages (VAC) L-L | 440 / 460 / 480 | |||||
| Phases | 3 phases / 2 phases | |||||
| Frequency (Hz) | 50-60 Hz | |||||
| Consume (W) | 169 | 362 | 359 | 420 | 786 | 897 |
| Max. constant current Amp | 60 | 125 | 185 | 240 | 365 | 590 |
| Impedance characteristic | 5% | |||||
| Impedance characteristic | 95% @ 110% charge / 80% @ 150% charge | |||||
| Overload | 200% @ 3 minutes maximum | |||||
| Current harmonic distortion reduction | 40% to 50% reduction in distortion, for loads greater than 50% of capacity | |||||
| Recommended maximum voltage unbalance | +_1% | |||||
| Filter type | Reject Reactor | |||||
| FAP-IND Model | 5330 | 5345 | 5350 | 53100 | 53150 | 53200 | 53300 | 53500 |
| Active Power, Apparent Power, Energy, Current and Power Factor | Class 0.5 (0.5% error) | |||||||
| Reactive Power | Class 1 (1% error) | |||||||
| Voltage and Frequency | Class 0.2 (0.2% error) | |||||||
| THDv – THDi | Class 1 (odd 1 – 31) (1% error) | |||||||
| International Standards | According to: IEC – CE – UE – RoHS | |||||||
| FAP-IND Model | 5330 | 5350 | 53100 | 53150 | 53200 |
| Dimensions H x W x D (mm) | 780 x 500 x 600 | ||||
| Weight (Kg) | 30 | 40 | 50 | 60 | 90 |
| Temperature range | -10°C to +40°C | ||||
| Relative humidity | From or up to 95% without condensation | ||||
| Cabinet | Steel with baked epoxy electrostatic painting | ||||
| Maximum operating altitude (m.a.s.l.) | 2000 meters above sea level | ||||
| FAP-IND Model | 5345 | 53100 | 53150 | 53200 | 53300 | 53500 |
| Dimensions H x W x D (mm) | 780 x 500 x 600 | |||||
| Weight (Kg) | 30 | 45 | 50 | 60 | 80 | 100 |
| Temperature range | -10°C to +40°C | |||||
| Relative humidity | From or up to 95% without condensation | |||||
| Cabinet | Steel with baked epoxy electrostatic painting | |||||
| Maximum operating altitude (m.a.s.l.) | 2000 meters above sea level | |||||
Instantly calculate equipment capacity by filling in the missing information: