The FAP-IND Harmonic Filter, designed to reduce harmonic current distortion, operates at frequencies of 50 Hz or 60 Hz, preventing malfunctioning of your equipment.
FAP-IND Model | 5330 | 5350 | 53100 | 53150 | 53200 |
Capacity (kVA) | 30 | 50 | 100 | 150 | 200 |
Voltages (VAC) L-L | 208/220/240 | ||||
Phases | 3 phases / 2 phases | ||||
Frequency (Hz) | 50-60 Hz | ||||
Consume (W) | 179 | 201 | 296 | 465 | 516 |
Max. constant current Amp | 92 | 143 | 275 | 412 | 534 |
Impedance characteristic | 5% | ||||
Impedance characteristic | 95% @ 110% charge / 80% @ 150% charge | ||||
Overload | 200% @ 3 minutes maximum | ||||
Current harmonic distortion reduction | 40% to 50% reduction in distortion, for loads greater than 50% of capacity | ||||
Recommended maximum voltage unbalance | +_1% | ||||
Filter type | Reject Reactor |
FAP-IND Model | 5345 | 53100 | 53150 | 53200 | 53300 | 53500 |
Capacity (kVA) | 45 | 100 | 150 | 200 | 300 | 500 |
Voltages (VAC) L-L | 440 / 460 / 480 | |||||
Phases | 3 phases / 2 phases | |||||
Frequency (Hz) | 50-60 Hz | |||||
Consume (W) | 169 | 362 | 359 | 420 | 786 | 897 |
Max. constant current Amp | 60 | 125 | 185 | 240 | 365 | 590 |
Impedance characteristic | 5% | |||||
Impedance characteristic | 95% @ 110% charge / 80% @ 150% charge | |||||
Overload | 200% @ 3 minutes maximum | |||||
Current harmonic distortion reduction | 40% to 50% reduction in distortion, for loads greater than 50% of capacity | |||||
Recommended maximum voltage unbalance | +_1% | |||||
Filter type | Reject Reactor |
FAP-IND Model | 5330 | 5345 | 5350 | 53100 | 53150 | 53200 | 53300 | 53500 |
Active Power, Apparent Power, Energy, Current and Power Factor | Class 0.5 (0.5% error) | |||||||
Reactive Power | Class 1 (1% error) | |||||||
Voltage and Frequency | Class 0.2 (0.2% error) | |||||||
THDv – THDi | Class 1 (odd 1 – 31) (1% error) | |||||||
International Standards | According to: IEC – CE – UE – RoHS |
FAP-IND Model | 5330 | 5350 | 53100 | 53150 | 53200 |
Dimensions H x W x D (mm) | 780 x 500 x 600 | ||||
Weight (Kg) | 30 | 40 | 50 | 60 | 90 |
Temperature range | -10°C to +40°C | ||||
Relative humidity | From or up to 95% without condensation | ||||
Cabinet | Steel with baked epoxy electrostatic painting | ||||
Maximum operating altitude (m.a.s.l.) | 2000 meters above sea level |
FAP-IND Model | 5345 | 53100 | 53150 | 53200 | 53300 | 53500 |
Dimensions H x W x D (mm) | 780 x 500 x 600 | |||||
Weight (Kg) | 30 | 45 | 50 | 60 | 80 | 100 |
Temperature range | -10°C to +40°C | |||||
Relative humidity | From or up to 95% without condensation | |||||
Cabinet | Steel with baked epoxy electrostatic painting | |||||
Maximum operating altitude (m.a.s.l.) | 2000 meters above sea level |
Instantly calculate equipment capacity by filling in the missing information: