The UPS-IND HF 1300 M1 model has a better performance, due to its faster and more efficient process. It favors a longer life (8 to 10 years) both in the UPS and in the Lithium Ion battery bank. The latter offers a 55% reduction in footprint and is 50% light
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Capacity (W/ VA) | 10000/10000 | 15000/15000 | 20000/20000 | 30000/30000 |
| Voltage (Vca) | 208/220 | |||
| Overload Protection | Thermal magnetic input circuit breaker and Thermal magnetic bypass circuit breaker | |||
| Voltage Range (Vac) | 156 a 260 (Line to Line): -29%, +18% | |||
| Phase | Three Phase Star, 3 Phases + Neutral + Ground, optional: Delta (3 Phases + Ground) | |||
| Frequency Range (Hz) | 40 ~ 70 | |||
| Input Power Factor | ≥ 0.99 at full load | |||
| THDi | ≤ 3% | |||
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| AC to AC Maximum Efficiency | 94 % | |||
| Overload Protection | Thermal magnetic output circuit breaker | |||
| Output Power Factor | 1.0 | |||
| Voltage (Vac) | 190/200/208 ±1%(L-L)±% | |||
| Voltage Regulation Range (Vac) | ≤+/- 1 % | |||
| Frequency (Hz) | 60 +/- 0.1% (Battery mode), Optional: 50 Hz | |||
| Waveform | Pure sinosoidal wave | |||
| Harmonic Distortion THDv | ≤ 1% (Linear load), ≤ 4% (Non linear load) | |||
| Transfer Time (ms) | 0.0 ms(True On Line) | |||
| Connection Type | Three Phase Star, 3 Phases + Neutral + Ground, optional: Delta (3 Phases + Ground) | |||
| Overload | << 105% continuous, 105% to 110% 60 min., 110% to 125% 10 min., 125% to 150% 60 s., > 150% immediate switch to Bypass | |||
| Energy return | Does not support energy return | |||
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Voltage (Vcd) | +120(96+120) | |||
| Battery Capacity | 50 Ah | |||
| Battery Type | 15 standard (extended time available upon request | |||
| Full load backup time (min) | 5 min Standard (Extended Time available upon request) | |||
| Maximum Load Current (A) | Maximum Load Current (A) 0.1 – 1C (default 0.5 C) | |||
| Internal Battery Bank | 1 package | 2 package | 3 package | |
| Useful life time | 8 to 10 years at 40ºC. At higher temperatures their useful life is considerably reduced. To keep the batteries healthy we recommend recharging them at least once every 3 months and to avoid damage recharge them every 6 months. | |||
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Audible Noise (dB) | <60, at 1 meter | <65, at 1 meter | ||
| Operating Temperature (°C) | -5 ~ 40 | |||
| Relative Humidity | 0 ~ 95% without Condensation | |||
| Maximum Operating Altitude (m.a.s.l.) | 2,000 at 100% | |||
| Cabinet | Baked electrostatic Epoxy coated Steel | |||
| Dimensions, height x width x depth (mm) | 1250 x 378 x 995 | |||
| UPS Weight (kg) | 93 / 135 / 150 | 94 / 177 / 170 | 94 / 177 / 172 | 112 / 220 / 198 |
| UPS packaged weight (kg) | 199 | 241 | 284 | |
| Model UPS-IND HF |
1310 M1
|
1315 M1
|
1320 M1
|
1330 M1
|
|---|---|---|---|---|
| Inverter | 3 level IGBT technology for higher efficiency and minimized interference to grid | |||
| Rectifier | High Efficiency PFC type with IGBT technology | |||
| Output Isolation Transformer | Optional | |||
| Battery Status | Real Time Online/Discharge Information | |||
| Thermal Dissipation (kBTU / h) | 2.05 | 3.07 | 4.10 | 6.15 |
| Internal Bypass | Two Bypass Modes: Automatic Static & Manual Bypass Switch for Maintenance | |||
| Paralleling | N + 1 (up to 4 units) | |||
| Certifications | UL-1778, CE-62040-1, CE 62040-2, ISO 9001:2015 | |||
| Communications Interface | RS485 + EPO, 5 dry contact output signals, 1 dry contact input, RS232, SNMP network card | |||
| Digital Touch Screen | Displays: Input and output voltage, Load capacity, Battery voltage, Operating Status Mimic and LEDs Indicators | |||
| Alarms | Low Battery, Abnormal Input, UPS Failure, etc. | |||
| Protection | Low Battery, Overload, Short Circuit, Over Temperature, etc. | |||