From here it is possible to know the main operating indicators of the UPS and to make configurations.

Guarantees the continuity of operation even under maintenance conditions.

Facilitates the monitoring of the equipment by issuing alerts to the user for quick action.

Allows the equipment to operate at 110V or 220V, giving it great versatility.
New high frecuency HF UPS is the optimum protection for complex electrical networks. Battery back up as well as voltage correction offer continuos protection to connected equipment.
|
UPS-IND HF
|
1206
|
1210
|
|
|---|---|---|---|
| Capacity (kVA / kW) | 6/5.4 (optional 6/6) | 10/9 (optional 10/10) | |
| Input Voltage (V) | 220 | ||
| Overload Protection | Thermomagnetic switch | ||
| Range (Accepted) | – 20%, + 25% (at full load) | ||
| Phases | 2 phases (2 wires + ground) | ||
| Frequency | 40 – 70 (autodetection) | ||
| Power Factor | 0.99 | ||
|
UPS-IND HF
|
1206
|
1210
|
|---|---|---|
| Output Power Factor | 1.0 | |
| Voltage (Vca) | 120 / 208 / 220 / 230 / 240 (adjustable) | |
| Voltage Regulation Range | ± 1% (typical) | |
| Frequency (Hz) | 50 / 60 ± 0.2% (battery mode) | |
| Wave Form | THD pure sinusoidal wave ≤ 1% (linear load), ≤ 3% (non-linear load) | |
| Transfer Time (ms) | 0.0 (on line) | |
| Overload | 105%-125% 10min, 125%-150% 5 min, 150%-200% 5 s, >200% 200 ms. | |
| Load unbalance capability | 100% | |
| Efficiency | 96% | |
|
UPS-IND HF
|
1206
|
1210
|
|---|---|---|
| Voltage (Vcd) | 192 standard (192 -240 adjustable) | |
| Battery Type | 12 volts 7.2 Ah / 12 volts 9 Ah (lead acid, maintenance-free) | |
| Battery Backup Time at Full Load (min) | 3 -5 min. at full load, 9-18 min. at half load | |
| Maximum Load Current (A) | 1.0 – 3.0 (adjustable) | |
| Battery Bank | Internal | |
|
UPS-IND HF
|
1206
|
1210
|
|---|---|---|
| Audible Noise (dB) | < 55, at 1 meter | |
| MTBF (h) | 233,000 | |
| Operational Temperature (°C) | 0 ~ 40 at full load, 50 at 90% of the load | |
| Relative Humidity | 0 ~ 95% without condensation | |
| Maximum Operating Altitude (mamsl) | 2,300 at 100% , 3,100 at 85% | |
| Cabinet | Electrostatic baked epoxy coated steel, NEMA type 1 | |
| Dimensions, height x width x depth (mm) | 720 x 250 x 660 | |
| Weight (kg) | 104 (68 w/o battery) | 128 (88 w/o battery) |
|
UPS-IND HF
|
1206
|
1210
|
|
|---|---|---|---|
| Conversion Type | On-line double conversion (online) | ||
| Rectifier | IGBT Technology | ||
| Inverter | PWM Technology with IGBT conmuted at 19.2 kHz | ||
| Inverter Configuration | H Bridge | ||
| Inverter Type | Pulse width modulated (PWM) | ||
| Battery Status | Real time Online/Discharge information with 3% precision | ||
| Thermal Dissipation (kBTU/h) | 1.8 | 3 | |
| Certifications | CE-IEC 62040 – 1, ISO 9001 : 2015, NOM-001-SCFT-1993 | ||
| Communication Interface | RS-232 + SNMP (EPO Dry contacts, USB, optional) | ||
| Monitor Screen | LCD screen indicates UPS operating status | ||
| Alarm | irregular power supply, low battery voltage & UPS malfunction | ||
Instantly calculate equipment capacity by filling in the missing information: