The UPS-IND HF 1300 R1 is an advanced solution that incorporates inverter technology, making it a versatile and efficient option for a wide range of applications. Designed specifically for the industrial sector, this equipment ensures continuity of power supply, protecting critical equipment and operational processes from unexpected interruptions.
Model |
UPS IND 1360 R1 | UPS IND 13120 R1 | UPS IND 13200 R1 |
Overload Protection | Thermomagnetic circuit breaker Normal Input and Bypass Input | ||
Nominal Voltage (Vac) | 120/208 – 127/220 – 220/380 – 230/400 – 240/415 – 254/440 – 266/460 – 277/480 | ||
Voltage Range (Vac) | -25% a +25% | ||
Phases | Three Phase Star (3 Phases + Neutral + Ground), Delta Optional (3 Phases + Ground) | ||
Frequency Range (Hz) | 60 Hz +/-10% (50 Hz optional) | ||
Factor de Potencia de Entrada | ≥ 0.99 at full load | ||
THDI | ≤ 5% to 100 non-linear load |
Model | UPS IND 1360 R1 | UPS IND 13120 R1 | UPS IND 13200 R1 |
72/80 | 108/120 | 180/200 | |
AC to AC max efficiency | 94% | ||
Overload protection | Thermomagnetic circuit breaker at output | ||
Output power factor | 0,9 | ||
Voltage (Vac) | 120/208 – 127/220 – 220/380 – 230/400 – 240/415 – 254/440 – 266/460 – 277/480 | ||
Voltage Regulation Range (Vac) | +/- 1% (Linear Load) | ||
Frequency (Hz) | 60 +/- 0.2% (on batteries) (50 Hz optional) | ||
Waveform | Pure Sine | ||
Harmonic Distortion THDV | THD ≤ 1% (linear load) | ||
Transfer Time (ms) | 0.0 milliseconds (Line Mode to Battery Mode) | ||
Connection Type | Three-phase Star (3 Phase + Neutral + Ground), Delta Optional (3 Phase + Ground) | ||
Overload | 101 to 105% continuous operation, 106% to 130% 10 min to bypass, 131% to 155% 1 min to bypass, > 150% immediate bypass |
Model | UPS IND 1360 R1 | UPS IND 13120 R1 | UPS IND 13200 R1 |
BUS Voltage (Vdc) | Adjustable 348 to 480 | ||
Battery Voltage | 12V | ||
Battery Type | Lead acid (sealed and maintenance free) (Lithium Optional) | ||
Maximum Charger Charging Current (A) | 40 amps | ||
Battery Bank | External |
Model | UPS IND 1360 R1 | UPS IND 13120 R1 | UPS IND 13200 R1 |
Audible noise (dB) | < 65, at 1 meter | ||
Operating temperature (°C) | -5 to 40 °C | ||
Relative Humidity | 0 ~ 95% non-condensing | ||
Maximum operating altitude (masl) | Up to 1500 masl at 100% (up to 2,000 masl with 1% drift per 100 m) | ||
Cabinet | Steel with baked-on electrostatic epoxy coating | ||
Dimensions, height x width x depth (mm) | 2000 x 600 x 800 | 2000 x 1000 x 800 | 2000 x 1000 x 800 |
UPS weight (kg) | 525 (without batteries) | 800 (without batteries) | 1150 (without batteries) |
Model | UPS IND 1360 R1 | UPS IND 13120 R1 | UPS IND 13200 R1 |
Inverter | 3 Level Inverter with PWM type IGBT technology | ||
Rectifier | High Efficiency PFC type with IGBT technology | ||
Output Isolation Transformer | Included | ||
Battery status | On-line and real-time discharge information | ||
Thermal dissipation (kBTU/h) (full load) | 27 | 41 | 68 |
Internal Static Bypass | Included | ||
Internal Bypass Maintenance | Included | ||
Paralleling | Up to 4 equipments | ||
Certifications | CE-62040-1, CE 62040-2, ISO 9001:2015, | ||
Communications interface | EPO, 12 dry contact signals (8 output 4 input), RS232/RS485, SNMP network card, Battery temperature sensor | ||
Digital touch screen display | Displays: Input and Output Voltage, Charging Capacity, Battery Voltage, Operating Status Mimic, LED Indicators, Power On and Off Buttons | ||
Alarms | Low Battery, Abnormal Input, UPS Failure, Over Load, etc. | ||
Protection | Low Battery, Overload, Short Circuit, Over Temperature, Under Voltage etc. |