Sturdy and dependable for protecting equipment from an array of electrical problems while providing necessary battery backup in case of power interruption.
|
Model
|
UPS-IND 1110 |
|---|---|
| Capacity (W/ VA) | 900/1000 |
| Overload Protection | Fuse |
| Voltage (Vca) | 120 |
| Accepted Voltage Range | + 23%, – 33% |
| Phases | 1 phase (2 wire + ground) |
| Frequency(Hz) | 60 ± 6% (50 ± 6% optional) |
| Input Power Factor | 0.90 on empty, > 0.95 at full load |
|
Modelo
|
UPS-IND 1110 |
|---|---|
| Output Power Factor | 0.9 |
| Voltage (Vca) | 120 |
| Voltage Regulation Range | ± 1% |
| Frequency (Hz) | 60 ± 0.2% (50 ± 0.2% opcional) |
| Wave Form | Pure THD Sinusoidal Wave Form ≤ 3% (linear load) |
| Transfer Time (ms) | 0.0 (online) |
| Overload | 125% for 60 s, 150% for 1 s |
|
Model
|
UPS-IND 1110 |
|---|---|
| Voltage (Vcd) | 36 |
| Battery Type | Lead Acid (Sealed & Maintenance Free) |
| Full load Backup Time (min) | 30 at 300 W |
| Full load Backup Time (min) | 30 a 300 W |
| Maximum Load Current (A) | 1 |
| Battery Bank | Internal |
|
Model
|
UPS-IND 1110 |
|---|---|
| Audible Noise (dB) | < 45, at 1 meter |
| MTBF (h) | 130,000 |
| Operational Temperature (°C) | 0 ~ 40 |
| Relative Humidity | 0 ~ 95% without condensation |
| Maximum Operation Altitude (masml) | 3,000 |
| Finish | Baked electrostatic epoxy coated steel |
| Dimensions, height x width x depth (mm) | 225 x 155 x 400 |
| UPS Weight (kg) | 14 / (7 without batteries) |
|
Model
|
UPS-IND 1110 |
|---|---|
| Conversion Type | Online Double Conversion |
| Rectifier | PFC Status Bridge Rectifier |
| Inverter Conmutation Elements | PWM Technology w/ IGBT conmuted at 9000 Hz |
| Inverter Configuration | H Bridge |
| Inverter Type | PWM Pulse Width Management |
| Battery Status | Real time Online/Discharge Information w/ 3% Precision |
| Thermal Dissipation (kBTU / h) | 0.3 |
| Certifications | UL, 1778, CE-IEC 62040 – 1, ISO 9001:2015, NOM-001-SCFT-1993 |
| Interfaz de comunicación | USB & RS232 Communication Port. SNMP Protocol & Power Software Compatible |
| Monochromatic LCD Screen | Backlight: Input/Output Voltage, Load Capacity, Battery Voltage LEDs indicate Operation Mode |
| Alarm | For: Low Battery Voltage, Overload, Short Circuit, Overheating |
Instantly calculate equipment capacity by filling in the missing information: