Lead Acid Batteries for UPS with premium AGM separator extends equipment life expectancy and protects from micro short circuits.
Nominal Voltage | 12 V |
Nominal Capacity (20 hr) | 24 Ah |
Dimensions (mm) (length x width x height) |
166 (± 2) x 175 (± 2) x 125 (± 2)(125 ± 21 Total Height with Terminal) |
Weight (kg) | 7.20 |
Terminal | T3 |
Container Material | ABS |
Rated Capacity | 24.0 Ah / 1.20 A (20 hr, 1.80 V/cell, 25 ˚C) 22.3 Ah / 2.23 A (10 hr, 1.80 V/cell, 25 ˚C) 20.4 Ah / 4.08 A (5 hr,1.75 V/cell, 25 ˚C) 18.4 Ah / 6.12 A (3 hr,1.75 V/cell, 25 ˚C) 15.1 Ah / 15.1 A (1 hr,1.60 V/cell, 25 ˚C) |
Max. Discharge Current | 360 A (5s) |
Internal Resistance | 14 m Ω |
Operating Temp.Range | |
Discharge | -15 ~ 50 ˚C |
Charge | 0 ~ 40 ˚C |
Storage | -15 ~ 40 ˚C |
Nominal Operating Temp. Range | 25 ± 3 ˚C |
Cycle Use | Initial Charging Current less than 7.2 A Voltage 14.4 ~ 15.0 V at 25 ˚C, Temp. Coefficient -30mV / ˚C |
Uso en Standby | No limit on Initial Charging Current Voltage 13.5 ~ 13.8 V a 25 ˚C, Temp. Coefficient -20mV / ˚C |
Capacity affected by Temperature | 103% = at 40 ˚C, 100% = at 25 ˚C, 86% = at 0 ˚C |
Self Discharge | INDUSCELL batteries may be stored for up to 6 months at 25 ˚C, and then a freshening charge is required. For higher temperatures the time interval will be shorter. |
Instantly calculate equipment capacity by filling in the missing information: