The batteries are ideal for UPS and can be used in various applications that require backup power.
Nominal Voltage | 12 V |
Nominal Capacity (20 hr) | 9.0 Ah |
Dimensions (mm) (length x width x height) |
151 (+ 2) x 65 (+ 1) x 93.5 (+ 1) (99.5 + 1 high including terminal) |
Weight (kg) |
2.52 |
Terminal |
T1 / T2 |
Container material | ABS |
Nominal Capacity |
9.00 Ah (20 hr, 0.450 A, 1.75 V/cell) 8.51 Ah (10 hr, 0.851 A, 1.75 V/cell) 7.75 Ah (5 hr, 1.55 A, 1.75 V/cell) 6.90 Ah (3 hr, 2.30 A, 1.75 V/cell) 5.98 (1 hr, 5.98 A, 1.60 V/cell) |
Maximum discharge current |
Maximum discharge current 135 A (5s) |
Internal resistance |
17 m Ω |
Operating temperature range | |
Download | -15 ~ 50 ˚C |
Load | 0 ~ 40 ˚C |
Storage | -15 ~ 40 ˚C |
Rated operating temperature range | 25 ± 3 ˚C |
Cyclic use |
Initial charge current less than 2.70 A, at a voltage of 14.4 ~ 15.0 V at 25˚C, Temperature Coefficient – 30 mV /˚C |
Standby usage |
Initial charge current less than 2.70 A, at a voltage of 13.5 ~ 13.8 V at 25˚C, Temperature Coefficient – 20 mV /˚C |
Capacity affected by temperature | A 40 ˚C = 103%, A 25 ˚C = 100%, A 0 ˚C = 86% |
Self-discharge | INDUSCELL batteries can be stored at 25˚C and should be recharged at least every 6 months for as long as they remain in storage. At higher temperatures, recharging should be done more frequently |
Instantly calculate equipment capacity by filling in the missing information: