Due to their capacity, sealed lead acid batteries for UPS are designed for demanding applications such as industries and heavy machinery.
| Nominal Voltage | 12 V |
| Nominal Rate (C, 1.67V/cell) | 750W/cell |
| Nominal Capacity (20HR) | 210 Ah |
| Dimensions (mm) (length x width x height) |
522(±2) x 240 (±2) x 218 (±3) x 224 (±2) |
| Weight (kg) | 65.3 |
| Type of terminal | M8 |
| Container material | ABS |
| Nominal Capacity |
210.0 Ah (21.0 A, 1.80V/cell) | 195.2Ah (24.4A, 1.80 V/cell) | 185.0 Ah (37.0A, 1.80 V/cell) | 163.5 (54.5A, 1.75 V/cell) | 133.6Ah (133.6A, 1.60 V/cell)
|
| Maximum discharge current | 2100 A (5s) |
| Internal resistance | 2.6 m Ω (approximately) |
| Operating temperature range | |
| Download | -20 ~ 55 ˚C |
| Load | -20 ~ 40 ˚C |
| Storage | -15 ~ 50 ˚C |
| Rated operating temperature range | 25 ± 3 ˚C |
| Maximum charging current (25ºC) | 52.5A |
| Charging voltage (25ºC) | Float: 2.25 – 2.30V/cell / Equalization: 2.30 – 2.40V/cell |
| Temperature rating | 100% a 25ºC | 86% a 0º C |
| Self-discharge | INDUSCELL batteries can be stored at 25˚C and should be recharged at least every 6 months for as long as they remain in storage. At higher temperatures, recharging should be done more frequently |
Instantly calculate equipment capacity by filling in the missing information: