AMCR (120 V)
|
5101
|
---|---|
Capacity (kVA / kW) | 1/1 |
Input Voltage (V) | 120 |
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (120 V)
|
5102
|
Capacity (kVA / kW) | 2/2 |
Input Voltage (V) | 120 |
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (120 V)
|
5103
|
Capacity (kVA / kW) | 3/3 |
Input Voltage (V) | 120 |
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (120 V)
|
5106
|
Capacity (kVA / kW) | 6/6 |
Input Voltage (V) | 120 |
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (120 V)
|
5110
|
Capacity (kVA / kW) | 10/10 |
Input Voltage (V) | 120 |
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (120 V)
|
5115
|
Capacity (kVA / kW) | 15/15 |
Input Voltage (V) | 120 |
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (120 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Capacity (kVA / kW) | 1/1 | 2/2 | 3/3 | 6/6 | 10/10 | 15/15 |
Input Voltage (V) | 120 | |||||
Overload Protection | Thermo-magnetic switch on the output/ fuse (varies by model) | |||||
Range (Accepted) | ± 15% | |||||
Operational Frequency | 60 ± 10%, does not alter frequency* | |||||
Harmonic Distortion | Less than 2 % THD | |||||
Power Factor | Does NOT alter, adaptable to load requirement |
* Tolerance available under evaluation of the Engineering department
AMCR (120 V)
|
5101
|
---|---|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5102
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5103
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5106
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5110
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5115
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Voltage Regulation Range | ± 5% | |||||
Power Supply Impedance | Less than 2% | |||||
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) | |||||
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) | |||||
Reset | Automatic (programmed at factory) | |||||
Reset Time | 3 second standard time ** |
** Factory configurable up to 6 kVA on request
AMCR (120 V)
|
5101
|
---|---|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Input / Output Connectors | Plug & 4 outlets (NEMA 5-15R) |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 140 x 160 x 300 |
Weight (kg) | 4 |
AMCR (120 V)
|
5102
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Input / Output Connectors | Plug & 4 outlets (NEMA 5-15R) |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 140 x 160 x 300 |
Weight (kg) | 6 |
AMCR (120 V)
|
5103
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Input / Output Connectors | Terminal block (clamps)** |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 180 x 220 x 390 |
Weight (kg) | 10 |
AMCR (120 V)
|
5106
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Input / Output Connectors | Terminal block (clamps)** |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 180 x 220 x 390 |
Weight (kg) | 14 |
AMCR (120 V)
|
5110
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Input / Output Connectors | Terminal block (clamps)** |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 460 x 270 x 450 |
Weight (kg) | 24 |
AMCR (120 V)
|
5115
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Input / Output Connectors | Terminal block (clamps)** |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 460 x 270 x 450 |
Weight (kg) | 32 |
AMCR (120 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use | |||||
Input / Output Connectors | Plug & 4 outlets (NEMA 5-15R) | Terminal block (clamps)** | ||||
Transformers | Electrolytic copper magnetic wire and silicon steel sheet | |||||
Cooling & Ventilation | Natural convection | |||||
Cabinet | Galvanized steel sheet metal | |||||
Paint Finish | Primer and electrostatic epoxy powder coating | |||||
Maximum Altitude Of Operation (mamsl) | 3,000 | |||||
Operational Temperature (°C) | 0 ~ 40 | |||||
Relative Humidity | 0 ~ 95% without condensation | |||||
Dimensions, height x width x depth (mm) | 140 x 160 x 300 | 180 x 220 x 390 | 460 x 270 x 450 | |||
Weight (kg) | 4 | 6 | 10 | 14 | 24 | 32 |
** Factory configurable up to 6 kVA on request
AMCR (120 V)
|
5101
|
---|---|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (120 V)
|
5102
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (120 V)
|
5103
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (120 V)
|
5106
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (120 V)
|
5110
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (120 V)
|
5115
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (120 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
High Frequency Noise Protection | PI Filter | |||||
Control Technology | Microcontroller | |||||
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) | |||||
Measurement Parameters | Voltage, current, power and kWh | |||||
Electronic Commutation | TRIACs |
AMCR (120 V)
|
5101
|
---|---|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (120 V)
|
5102
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (120 V)
|
5103
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (120 V)
|
5106
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (120 V)
|
5110
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (120 V)
|
5115
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (120 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Transformer | Type H | |||||
Spike Suppressor | Varistors on the output | |||||
Efficiency | 98% minimum | |||||
Overload Capacity | Up to 400% in intermittent startups |
AMCR (220 V)
|
5101
|
---|---|
Capacity (kVA / kW) | 1/1 |
Input Voltage (V) | 220 |
Overload Protection | Thermo magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (220 V)
|
5102
|
Capacity (kVA / kW) | 2/2 |
Input Voltage (V) | 220 |
Overload Protection | Thermo magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (220 V)
|
5103
|
Capacity (kVA / kW) | 3/3 |
Input Voltage (V) | 220 |
Overload Protection | Thermo magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (220 V)
|
5106
|
Capacity (kVA / kW) | 6/6 |
Input Voltage (V) | 220 |
Overload Protection | Thermo magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (220 V)
|
5110
|
Capacity (kVA / kW) | 10/10 |
Input Voltage (V) | 220 |
Overload Protection | Thermo magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (220 V)
|
5115
|
Capacity (kVA / kW) | 15/1 |
Input Voltage (V) | 220 |
Overload Protection | Thermo magnetic switch on the output/ fuse (varies by model) |
Range (Accepted) | ± 15% |
Operational Frequency | 60 ± 10%, does not alter frequency* |
Harmonic Distortion | Less than 2 % THD |
Power Factor | Does NOT alter, adaptable to load requirement |
AMCR (220 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Capacity (kVA / kW) | 1/1 | 2/2 | 3/3 | 6/6 | 10/10 | 15/1 |
Input Voltage (V) | 220 | |||||
Overload Protection | Thermo magnetic switch on the output/ fuse (varies by model) | |||||
Range (Accepted) | ± 15% | |||||
Operational Frequency | 60 ± 10%, does not alter frequency* | |||||
Harmonic Distortion | Less than 2 % THD | |||||
Power Factor | Does NOT alter, adaptable to load requirement |
* Tolerance available under evaluation of the Engineering department
AMCR (120 V)
|
5101
|
---|---|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5102
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5103
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5106
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5110
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5115
|
Voltage Regulation Range | ± 5% |
Power Supply Impedance | Less than 2% |
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) |
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) |
Reset | Automatic (programmed at factory) |
Reset Time | 3 second standard time ** |
AMCR (120 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Voltage Regulation Range | ± 5% | |||||
Power Supply Impedance | Less than 2% | |||||
Sustained High/Low Voltage Protection | Contactor or relay on the output, automatic shut off (varies by model) | |||||
Correction Time | Immediate, (8.3 milliseconds, 1/2 cycle) | |||||
Reset | Automatic (programmed at factory) | |||||
Reset Time | 3 second standard time ** |
** Factory configurable up to 6 kVA on request
AMCR (220 V)
|
5101
|
---|---|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 180 x 220 x 390 |
Weight (kg) | 8 |
AMCR (220 V)
|
5102
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 180 x 220 x 390 |
Weight (kg) | 10 |
AMCR (220 V)
|
5103
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 180 x 220 x 390 |
Weight (kg) | 12 |
AMCR (220 V)
|
5106
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 180 x 220 x 390 |
Weight (kg) | 17 |
AMCR (220 V)
|
5110
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 460 x 270 x 450 |
Weight (kg) | 28 |
AMCR (220 V)
|
5115
|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use |
Transformers | Electrolytic copper magnetic wire and silicon steel sheet |
Cooling & Ventilation | Natural convection |
Cabinet | Galvanized steel sheet metal |
Paint Finish | Primer and electrostatic epoxy powder coating |
Maximum Altitude Of Operation (mamsl) | 3,000 |
Operational Temperature (°C) | 0 ~ 40 |
Relative Humidity | 0 ~ 95% without condensation |
Dimensions, height x width x depth (mm) | 460 x 270 x 450 |
Weight (kg) | 35 |
AMCR (220 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Recommended Use | Domestic, commercial and/or industrial, non vibratory, indoor use | |||||
Transformers | Electrolytic copper magnetic wire and silicon steel sheet | |||||
Cooling & Ventilation | Natural convection | |||||
Cabinet | Galvanized steel sheet metal | |||||
Paint Finish | Primer and electrostatic epoxy powder coating | |||||
Maximum Altitude Of Operation (mamsl) | 3,000 | |||||
Operational Temperature (°C) | 0 ~ 40 | |||||
Relative Humidity | 0 ~ 95% without condensation | |||||
Dimensions, height x width x depth (mm) | 180 x 220 x 390 | 460 x 270 x 450 | ||||
Weight (kg) | 8 | 10 | 12 | 17 | 28 | 35 |
** Factory configurable up to 6 kVA on request
AMCR (220 V)
|
5101
|
---|---|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (220 V)
|
5102
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (220 V)
|
5103
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (220 V)
|
5106
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (220 V)
|
5110
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (220 V)
|
5115
|
High Frequency Noise Protection | PI Filter |
Control Technology | Microcontroller |
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) |
Measurement Parameters | Voltage, current, power and kWh |
Electronic Commutation | TRIACs |
AMCR (220 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
High Frequency Noise Protection | PI Filter | |||||
Control Technology | Microcontroller | |||||
Monitoring (Operational Status) | LEDs / Digital display with LEDs (vary by model) | |||||
Measurement Parameters | Voltage, current, power and kWh | |||||
Electronic Commutation | TRIACs |
AMCR (220 V)
|
5101
|
---|---|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (220 V)
|
5102
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (220 V)
|
5103
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (220 V)
|
5106
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (220 V)
|
5110
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (220 V)
|
5115
|
Transformer | Type H |
Spike Suppressor | Varistors on the output |
Efficiency | 98% minimum |
Overload Capacity | Up to 400% in intermittent startups |
AMCR (220 V)
|
5101
|
5102
|
5103
|
5106
|
5110
|
5115
|
---|---|---|---|---|---|---|
Transformer | Type H | |||||
Spike Suppressor | Varistors on the output | |||||
Efficiency | 98% minimum | |||||
Overload Capacity | Up to 400% in intermittent startups |
Instantly calculate equipment capacity by filling in the missing information: