Uninterruptible Power Supply (UPS)

UPS-IND 1300 MR

Uninterruptible Power Supply (UPS)

UPS-IND 1300 MR

10~100 kVA
Capacity
+/-1%
Voltage regulation
2 Year Warranty

The Modular UPS is specifically designed for data centers and computer sites. ECO-IND function activates the inverter automatically for maximum energy efficiency. Reliable features and battery back up offer full protection for data management and security.

  • On Line Double Conversion
  • Power Factor Correction
  • Parallelable Technology
  • Cold Start Function
  • Smart Ventilation Control
  • ECO-IND Mode
  • IGBT Technology
  • Maintenance Bypass
  • Electronic Bypass

Uninterrupted Power

Icono rayo
On Line Double Conversion
Guarantees clean and stable voltage output despite irregularities on the input.
Icono rayo
Power Factor Correction
Reduces gap between voltage and current for higher efficiency and functionality.
Icono rayo
Parallelable Technology
Parallel by capacity or redundancy n + 1 (master-slave exempt).
Icono rayo
Cold Start Function
Autonomous operation initiates directly from batteries.
Icono rayo
Smart Ventilation Control
Automatic vent adapts speed in proportion to variations in demand or room temperature.
Icono rayo
ECO-IND Mode
99% efficiency ECO Mode while voltage and frequency are within safe range.
Icono rayo
IGBT Technology
High efficiency and fast switching controller that adapts to high power applications.
Icono rayo
Maintenance Bypass
Bypass switch enables safe UPS electrical isolation during maintenance or testing.

Designed with Durable & Resistant Materials

Industronic UPS has been designed with the highest standard for long lasting reliable performance.

Learn more

Applications

Banks
Banks
Call Centers
Call Centers
Computer Rooms
Computer Rooms
Financial Institutions
Financial Institutions
Medical Equipment
Medical Equipment
Regional Office Building
Regional Office Building
Robotics
Robotics
Telecommunication
Telecommunication

Technical Specifications

UPS-IND 1300 MR
1310
1320
1330
1340
1350
1360
1370
1380
1390
13100
Capacity (kVA / kW) 10/9 20/18 30/27 40/36 50/45 60/54 70/63 80/72 90/81 100/90
Input Voltage (V) 120 / 208 or 127 / 220
Range (Accepted) – 15 %, + 25 %
Phases Star, Three Phase (4 wires + ground)
Frequency 60 ± 10%, (optional 50 ± 10%)
Synchronization Frequency Range (Hz) 50 / 60 ± 5 % (optional ± 10 % )
Power Factor 0.99
Bypass Voltage Range +15 % (optional +10 %, +20%) / – 15 % (optional – 20 %, – 30%)
UPS-IND 1300 MR
1310
1320
1330
1340
1350
1360
1370
1380
1390
13100
THDI Resistive load: ≤ 3%; Non linear load: ≤ 5%
Output Power Factor 0.9
Voltage (Vca)e 120 / 208 or 127/220 ( + 1%), for balanced & unbalanced loads
Voltage Regulation Range ± 1%
Frequency (Hz) Automatic line synchronization 60 + 0.1%
Wave Form Sinusoidal wave
Transfer Time (ms) 0.0 (on line)
3 Phase Disphasing With balanced load ≤ 2°; with unbalanced load ≤ 5°
Wave Form Distorsion (THDv) Linear load ≤ 3%; Non linear load ≤ 6%
Bypass Switch Time Linear load ≤ 3%; Non linear load ≤ 6%
System Efficiency In ECO mode 99%, w/ online inverter ≥ 94%; w/ battery inverter ≥ 97%
Overload Capacity 105% at 115% for 60 min, 116% at 130% for 10 min, 131% at 150% for 1 min, ≥ 151% automatically reverts to bypass
Module Current Equalizer ≤ 5%
Output DC Component ≤ 100 mV
Transient Dynamic Range Responser From 0% to 100% or from 100% to 0%, output voltage ≤ 5%
Unbalanced Load Capacity Withstands up to 100% unbalanced load
UPS-IND 1300 MR
1310
1320
1330
1340
1350
1360
1370
1380
1390
13100
Voltage (Vcd) 216 (12 volts – 36 batteries)
Battery Type Lead acid (sealed and maintenance free)
Battery Backup Time 10 minutes at 100% w/ 1 battery pack per 10 kVA module
Maximum Load Current (A) Proportional to modules installed, maximum 100
Dimensions: height x width x depth (mm) Internal 2000 x 600 x 1150
Charger Included in each power module, 2 Amp capacity per module
UPS-IND 1300 MR
1310
1320
1330
1340
1350
1360
1370
1380
1390
13100
Audible Noise (dB) 50 to < 58, at 1 meter distance, (depends on the load)
Operational Temperature (°C) 0~40
Relative Humidity 0 ~ 95% without condensation
Maximum Operating Altitude (mamsl) 2,000
Cooling Type Forced air
Dimensions, height x width x depth (mm) 2000 x 600 x 1100 2000 x 600 x 800
Weight (kg) System (w/o modules): 275 / ea. module 25.5
UPS-IND 1300 MR
1310
1320
1330
1340
1350
1360
1370
1380
1390
13100
Conversion Type On line double conversion, microprocessor controlled
Inverter IGBT technology
Rectifier IGBT technology
Internal Bypass Two: electronic (automatic) bypass, and manual bypass for maintenance/repair
Certifications CE-IEC-EN 62040-1, CE-IEC-EN 62040-2, ISO 9001:2015, NOM
Communication Interface Dry contacts, RS232 /RS485 & SNMP card, Web, Ethernet, TCP/IP, HTTP, HTTPS
Touchscreen Monitor Parameters Displayed Three phase voltage input, input frequency, three phase voltage output, battery voltage battery charge/discharge current, output current by module, internal temperature by module, parameter adjustment, event history, etc.
LED Indicator UPS status & failure indicator
Alarm Abnormal output, low battery, overload, failure
Protection Short circuit, over/low voltage, overheating, low battery, abnormal communication, etc.