Uninterruptible Power Supply (UPS)

UPS-IND 1300

Uninterruptible Power Supply (UPS)

UPS-IND 1300

40~60 kVA
Capacity
+/-1%
Voltage regulation
2 Year Warranty

Reliable, continuous power with complete battery for back up. Cool Start function extends product lifetime and operation efficiency.

  • On Line Double Conversion
  • Power Factor Correction
  • Smart Battery Management
  • Cold Start Function
  • Smart Ventilation Control
  • ECO-IND Mode
  • SNMP Network Card
  • IGBT Technology
  • Isolation Transformer

Uninterrupted Power

Icono rayo
On Line Double Conversion
Guarantees clean and stable voltage output despite irregularities on the input.
Icono rayo
Power Factor Correction
Reduces gap between voltage and current for higher efficiency and functionality.
Icono rayo
Smart Battery Management
Monitors and charges batteries to ensure optimum efficiency and use.
Icono rayo
Cold Start Function
Autonomous operation initiates directly from batteries.
Icono rayo
Smart Ventilation Control
Automatic vent adapts speed in proportion to variations in demand or room temperature.
Icono rayo
ECO-IND Mode
99% efficiency ECO Mode while voltage and frequency are within safe range.
Icono rayo
IGBT Technology
High efficiency and fast switching controller that adapts to high power applications.
Icono rayo
SNMP Network Card
Monitoring equipment alerts, controls and tracks current status of UPS from any off site location.
Icono rayo
Isolation Transformer
Isolated, high level functionality for operational continuity during a power malfunction.

Applications

Buildings
Buildings
Commercial buildings
Commercial buildings
Commercial Security Systems
Commercial Security Systems
Computer Rooms
Computer Rooms
Industry
Industry
Machinery
Machinery
Medical Equipment
Medical Equipment
Penitentiaries
Penitentiaries

Technical Specifications

UPS-IND
1362
1366
1370
Capacity (kVA / kW) 40/36 50/45 60/54
Input Voltage (V) 120 / 208, 127 / 220, 220 / 380, 254 / 440 or 277 / 480
Overload Protection Thermomagnetic switch & bypass
Range (Accepted) + 20% at 100% of the load, + 25% at 75% and + 30% at 50%
Phases Star: 3 phase star (4 wires + ground) / Delta: (optional) 3 phases (3 wires + ground)
Frequency 60 ± 10 % (optional 50 ± 10 % )
Power Factor 0.90 when empty > 0.95 at full load
UPS-IND
1362
1366
1370
Overload Protection Thermomagnetic switch on the output
Output Power Factor 0.9
Voltage (Vca) 120 / 208, 127 / 220, 220 / 380, 254 / 440 or 277 / 480
Voltage Regulation Range ± 1% (typical)
Frequency (Hz) 60 ± 0.2% (optional 50 ± 0.2%)
Wave Form THD pure sinusoidal wave ≤ 1% (linear load), ≤ 3% (non-linear load)
Transfer Time (ms) 0.0 (on line)
Connection Type Star (3 phases, 4 wires + ground)
Overload 125% of nominal load for 10 min; 150% for 60 s
UPS-IND
1362
1366
1370
Voltage (Vcd) 348
Battery Type Lead acid (sealed, maintenance free)/ (optional: nickel cadmium)
Battery Backup Time at Full Load (min) 5
Maximum Load Current (A) 40
Battery Bank External
Dimensions, height x depth x width (mm) 660 x 820 x 1600
Weight w/o batteries (kg) 351 419 656
UPS-IND
1362
1366
1370
Audible Noise (dB) < 65, to 1 meter
MTBF (h) 233,000
Operational Temperature (°C) 0~40
Relative Humidity 0 ~ 95% without condensation
Maximum Operating Altitude (mamsl) 2,000 at 100% & 3,000 at 96%
Cabinet Electrostatic baked epoxy coated steel
Dimensions, height x width x depth (mm) 1600 x 800 x 800
Weight (kg) 590 620 670
UPS-IND
1362
1366
1370
Conversion Type On-Line double conversion
Rectifier Full wave SCR generates 6 pulses & phase control
Inverter Conmutation Elements PWM pulse width modulated w/ IGBT conmutated at 9000 Hz
Filters Anti harmonics (2% RMS distortion)
Isolation Transformer Dry transformer included on the output
Battery Status Real time Online/Discharge information with 3% precision
Thermal Dissipation (kBTU/h) 12.1 15.2 18.2
Internal Bypass Two: electronic (automatic) bypass, and manual bypass for maintenance/repair
Paralleling n+1 up to 4 units
Certifications CE-IEC 62040 -1, ISO 9001:2015, NOM
Communication Interface RS485, dry contact relay signal, SNMP network card (included) or MODBUS ethernet w/ one port per unit and two ports in parallel
LCD Monochromatic Screen Backlight: Input/Output voltage, load capacity, battery voltage, operating status
Alarm Overload, abnormal alternate current on the input, low battery
Protection Low battery, overheating, short circuit, overvoltage on the output, low voltage on the output

Power Calculator