UPS Battery

BPA-IND-F 70A Long Life

UPS Battery

BPA-IND-F 70A Long Life

12 V 70 Ah
Capacity
2 Year Warranty

Long life float service design and high energy density, with front terminals, used in back-up power for UPS system and communication

  • 12 year design life (25°C)
  • Front terminals
  • Unique design of the ventilation valve
  • Maintenance Free
  • Augmented Resistance
  • AGM Separator
  • Gas Recombination
  • Superior Materials
Icono rayo
12 year design life
Thick plates, special formula of paste and plate making process for a long service life (12 years at 25°C).
Icono rayo
Front terminals
The front terminals make installation, maintenance and monitoring easy.
Icono rayo
Maintenance Free
Sealed Lead Acid Batteries require zero maintenance.
Icono rayo
Augmented Resistance
Battery case with ABS materials for increased heat and impact resistance.
Icono rayo
AGM Separator
Withstands low temperatures, has low self discharge and significantly extends life expectancy.
Icono rayo
Gas Recombination
Gasses recombine to create humidity which reduces maintenance and lowers gassing.
Icono rayo
Superior Materials
High Purity Lead Acid Batteries ensure low self discharge.

Technical Specifications

Nominal Voltage 12 V
Nominal Capacity (C ,1.80V/cell) 70 Ah
Dimensions (mm)
(length x width x height)
564 ( ± 2) x 114 ( ± 1.5) x 187 ( ± 2);(187 ± 2 Total height with terminal)
Weight (kg) 25.5
Terminal M6
Container Material ABS
Rated Capacity 74.6 Ah (20 hr, 3.73 A, 1.80 V/cell)
70.0 Ah (10 hr, 7.0 A, 1.80 V/cell)
68.4 Ah (8 hr, 8.55 A, 1.75 V/cell)
61.5 Ah (5 hr, 12.3 A,1.75 V/cell)
44.8 Ah (1 hr, 44.8 A,1.67 V/cell)
Max. Discharge Current 700 A (5s)
Internal Resistance 5.2 m Ω (approx.)
Operating Temp.Range
Discharge -15 ~ 50 ˚C
 Charge 0 ~ 40 ˚C
Storage -15 ~ 40 ˚C
Nominal Operating
Temperature Range
25 ± 3 ˚C
Cycle Use Initial Charging Current less than 30.0 A. Voltage 14.1 ~ 14.4 V at 25 ˚C, Temp. Coefficient – 30 mV / ˚C
Uso en Standby Initial Charging Current less than 30.0 A.Voltage 13.5 ~ 13.8 V a 25 ˚C, Temp. Coefficient – 20 mV / ˚C
Capacity affected
by Temperature
103% = at 40 ˚C,
100% = at 25 ˚C,
86% = at 0 ˚C
Self Discharge INDUSCELL batteries may be stored for up to 6 months at 25 ˚C, and then a freshening charge is required. For higher temperatures the time interval will be shorter.

Power Calculator

Instantly calculate equipment capacity by filling in the missing information:

Cerrar
Whatsapp Whatsapp