High purity lead batteries provide minimum self discharge and reliable backup.
Nominal Voltage | 12 V |
Nominal Capacity (20 hr) | 7.2 Ah |
Dimensions (mm) (length x width x height) |
151 (± 2) x 65 (± 1) x 93.5 (± 1)(99 ± 1 Total height with terminal) |
Weight (kg) | 2.35 |
Terminal | T2 |
Container Material | ABS |
Rated Capacity | 7.20 Ah / 0.36 A (20 hr, 1.80 V/cell, 25 ˚C) 6.70 Ah / 0.67 A (10 hr, 1.80 V/cell, 25 ˚C) 6.12 Ah / 1.22 A (5 hr,1.75 V/cell, 25 ˚C) 5.37 Ah / 1.79 A (3 hr,1.75 V/cell, 25 ˚C) 4.49 Ah / 4.49 A (1 hr,1.60 V/cell, 25 ˚C) |
Max. Discharge Current | 108 A (5s) |
Internal Resistance | 18 m Ω |
Operating Temp.Range | |
Discharge | -15 ~ 50 ˚C |
Charge | 0 ~ 40 ˚C |
Storage | -15 ~ 40 ˚C |
Nominal Operating Temperature Range |
25 ± 3 ˚C |
Cycle Use | Initial Charging Current less than 2.16 A Voltage 14.4 ~ 15.0 V at 25 ˚C, Temp. Coefficient -30mV / ˚C |
Uso en Standby | No limit on Initial Charging Current Voltage 13.5 ~ 13.8 V a 25 ˚C, Temp. Coefficient -20mV / ˚C |
Capacity affected by Temperature |
103% = at 40 ˚C, 100% = at 25 ˚C, 86% = at 0 ˚C |
Self Discharge | INDUSCELL batteries may be stored for up to 6 months at 25 ˚C, and then a freshening charge is required. For higher temperatures the time interval will be shorter. |
Instantly calculate equipment capacity by filling in the missing information: