UPS Battery

BPA-IND 7.2

UPS Battery

BPA-IND 7.2

12 V 7.2 Ah
Voltage
2 Year Warranty

High purity lead batteries provide minimum self discharge and reliable backup.

  • Maintenance Free
  • Lead Calcium Grill
  • Augmented Resistance
  • AGM Separator
  • Gas Recombination
  • Superior Materials

 

Icono rayo
Maintenance Free
Sealed Lead Acid Batteries require zero maintenance.
Icono rayo
Lead Calcium Grills
Reduced gassing, self discharge and corrosion to provide long life expectancy and optimum operation.
Icono rayo
Augmented Resistance
Battery case with ABS materials for increased heat and impact resistance.
Icono rayo
AGM Separator
Withstands low temperatures, has low self discharge and significantly extends life expectancy.
Icono rayo
Gas Recombination
Gasses recombine to create humidity which reduces maintenance and lowers gassing.
Icono rayo
Superior Materials
High Purity Lead Acid Batteries ensure low self discharge.

Applications

Aircraft transmitter
Aircraft transmitter
Automatic Control Systems
Automatic Control Systems
Communication Power Supply
Communication Power Supply
DC Power Supply
DC Power Supply
Electronic equipment and accessories
Electronic equipment and accessories
Emergency Backup Power Supply
Emergency Backup Power Supply
Emergency lighting
Emergency lighting
Railway transmitters
Railway transmitters

Technical Specifications

Nominal Voltage 12 V
Nominal Capacity (20 hr) 7.2 Ah
Dimensions (mm)
(length x width x height)
151 (± 2) x 65 (± 1) x 93.5 (± 1)(99 ± 1 Total height with terminal)
Weight (kg) 2.35
Terminal T2
Container Material ABS
Rated Capacity 7.20 Ah / 0.36 A (20 hr, 1.80 V/cell, 25 ˚C)
6.70 Ah / 0.67 A (10 hr, 1.80 V/cell, 25 ˚C)
6.12 Ah / 1.22 A (5 hr,1.75 V/cell, 25 ˚C)
5.37 Ah / 1.79 A (3 hr,1.75 V/cell, 25 ˚C)
4.49 Ah / 4.49 A (1 hr,1.60 V/cell, 25 ˚C)
Max. Discharge Current 108 A (5s)
Internal Resistance 18 m Ω
Operating Temp.Range
Discharge -15 ~ 50 ˚C
 Charge 0 ~ 40 ˚C
Storage -15 ~ 40 ˚C
Nominal Operating
Temperature Range
25 ± 3 ˚C
Cycle Use Initial Charging Current less than 2.16 A Voltage 14.4 ~ 15.0 V at 25 ˚C, Temp. Coefficient -30mV / ˚C
Uso en Standby No limit on Initial Charging Current Voltage
13.5 ~ 13.8 V a 25 ˚C, Temp. Coefficient -20mV / ˚C
Capacity affected
by Temperature
103% = at 40 ˚C,
100% = at 25 ˚C,
86% = at 0 ˚C
Self Discharge INDUSCELL batteries may be stored for up to 6 months at 25 ˚C, and then a freshening charge is required. For higher temperatures the time interval will be shorter.